Troubleshooting ESP Voltage Dividers

ESP Tech Tips

Ensuring accurate operating signals to voltage controls is the key to optimizing precipitator performance and protecting your equipment. Proper maintenance yields significant long-term benefits.

Maintaining peak performance for precipitator voltage controls requires accurate transformer/rectifier (T/R) feedback signals. These signals are also important tools for troubleshooting sections with poor performance. One of the most important feedback signals is secondary voltage or kV. Although this is one of the most commonly inaccurate signals found in many installations, correcting these errors is relatively simple.

One clue that kV feedback is inaccurate: secondary voltage is operating at unusually low levels, yet the primary voltage indication is normal for the amount of current displayed. If this happens, you can check for inaccuracies by estimating the secondary voltage and comparing the estimate to the actual reading.

Use the following formula to estimate secondary voltage.

Primary Current x Primary Voltage x .7
              Secondary Current

Here’s an example: a T/R set is running 73 Amps, 440 Volts and 500 Ma (.5A). In this case, you’d fill in the formula as shown below.

73A x 440V x .7 = 44,968 Volts or 45 kV
.5A

This method of calculating secondary voltage is a useful troubleshooting tool when you experience a missing or suspicious signal. The formula only works, though, if the conduction angle is above 100 and the other three signals are calibrated.

If you discover that the signal is not, in fact, reading correctly, the next step is to recalibrate and verify the signal using the control manufacturer’s guidelines. Be very cautious when calibrating feedback signals: you’re working on a live control with high voltage!

Signals from voltage dividers allow the voltage control to read and monitor secondary voltage. This protects the T/R set from over-voltage, which can damage diode bridges and the secondary transformer. How can you tell if a voltage divider has failed or is failing? You can reasonably suspect this in the following scenario: a voltage control shows no reading in the secondary voltage readout display, but it is still operating and the other readout values are normal.

When a voltage divider fails, replace it. Many voltage dividers are located in the T/R set tank, which makes them difficult to access. Retrofit dividers are available that can be installed in the high voltage switch enclosure or bus duct”a much more accessible location.

Optimizing Voltage Controls for Maximum Efficiency

  1. Understanding Voltage-Current Relationships
    • Monitor voltage and current trends to detect inefficiencies in charging and collection.
    • Ensure that the transformer-rectifier set is operating at optimal voltage levels to maintain strong corona discharge.  
  2. Adjusting Voltage for Load Conditions
    • Confirm voltage controls are adapting to changes in process conditions and particulate load.
  3. Routine Maintenance of Voltage Control Components
  4. Utilizing Advanced Monitoring Systems
    • Implement real-time voltage monitoring to proactively detect issues before they affect ESP efficiency.
    • Use data analytics to optimize voltage control strategies and improve collection performance.

From Our Optimized Insights

Latest Insights

  • News Article

    2025: A Year of Milestones, Momentum, and Gratitude

    As we reach the close of 2025, I want to take a moment to reflect on the progress we’ve made together during a year filled with meaningful achievements and important transitions. First, I’m proud to share that we completed another year with zero safety incidents. Safety is foundational to…

  • News Article

    Celebrating 50 Years of Neundorfer!

    This year marks a milestone: Neundorfer’s 50th Anniversary. For half a century, we’ve been driven by innovation, collaboration and a commitment to helping our partners solve complex challenges in smarter, more sustainable ways. In August, we gathered with employees, partners, and friends to celebrate this achievement. It was…

  • News Article

    2024 in Review: Success, Sustainability, and Milestones

    2024 in Review: Success, Sustainability, and Milestones As the year draws to a close, I want to take a moment to reflect on the successes we’ve achieved and the milestones we’ve reached together. This has been a remarkable year—one that saw us successfully complete numerous projects, welcome…